| Penetration | | System | | Building Element | | FRL | | Product | | Application / Mounting Detail | | Approval Ref. | | Max. Size | | Condition |
| Wall | | WM1 | | Masonry | | -/120/- | | LVH44 | | Mounted in steel casing in penetration | | FCO2643, FCO1741 | | 1200mm x >10m, >10m x 1200mm | | |
| | | WM2 | | Masonry | | -/240/- | | LVH44 Cased | |
Steel casing in penetration | | C91525 | | 250 x 250mm | | |
| | | WM3 | | Masonry | | -/120/- | | LVH44 | | NO casing in penetration | | FCO2643 | | 600mm x >10m, >10m x 600mm | | |
| | | WM4 | | Masonry | | -/120/- | | LVH44 | | NO casing - surface mounted over penetration | | FCO1740 | | 600 x 600mm | | max hole size 500mm x 500mm |
| | | WM5 | | Masonry | | -/120/- | | LVH-O | | Steel sleeve in penetration | | 22774-01 | | 450mm diameter | | |
| | | WM6 | | Masonry | | -/240/- | | LVH-O | | Steel sleeve in penetration | | 22774-01 | | 150mm diameter | | |
| | | WM7 | | Masonry | | -/120/- | | LVH-OSS | | Stainless steel sleeve in penetration | | 22774-01 | | 450mm diameter | | |
| | | WM8 | | Masonry | | -/120/- | | LVH-O | | Spiral duct sleeve grouted into penetration (angle free) | | FCO2008 | | 300mm diameter | | |
| | | WM9 | | Masonry | | -/120/- | | LVH Hi-Flo | | Mounted in steel casing in penetration | | FCO2568 | | 250mm x 400mm | | |
| | | WM10 | | Masonry | | -/120/- | | LVHO Hi-Flo | | Steel sleeve in penetration | | FCO2568 | | 250mm diameter | | |
| | | WM11 | | Masonry | | -/120/- | | LVH44 | | NO casing with various fixing brackets | | FCO1854,
FC02512 | | 600mm x >10m | | |
| | | | | | | | | | | | | | | | | |
| | | WH1 | | Hebel 75SS | | -/120/- | | LVH44 | | Mounted in steel casing in penetration | | FCO2325 | | 1200 H x 600mm W *dual panel | | 400mm max if in single in panel |
| | | WH2 | | Hebel 75SS | | -/120/- | | LVH-O | |
Steel sleeve in penetration | | FCO2325 | | 450mm dia. *dual panel | | 400mm max if in single in panel |
| | | WH3 | | Hebel 75SW | | -/120/- | | LVH44 | | Mounted in steel casing in penetration | | FCO2325 | | 1200 H x 600mm W *dual panel | | 400mm max if in single in panel |
| | | WH4 | | Hebel 75SW | | -/120/- | | LVH-O | |
Steel sleeve in penetration | | FCO2325 | | 450mm dia. *dual panel | | 400mm max if in single in panel |
| | | WH5 | | Hebel 75SW | | -/120/- | | LVH44 | |
Mounted in steel casing tight to underside of slab | | FCO2495 | | 300mm x 300mm | | |
| | | WH6 | | Hebel 75SW | | -/120/- | | LVH-O | |
Steel sleeve positioned tight to underside of slab | | FCO2495 | | 150mm diameter | | |
| | | WH7 | | Hebel 75SW | | -/120/- | | LVH44 | |
Mounted in steel casing tight to underside of slab with 3 angles | | FCO2495 | | 300mm x 300mm | | |
| | | | | | | | | | | | | | | | | |
| | | WS1 | | CSR Security wall | | -/90/90 | | LVH44 | | Mounted in steel casing in penetration | |
WFRA45955 | | 600 x 600mm | | |
| | | WS2 | | CSR Security wall | | -/90/- | | LVH-O | | Steel sleeve in penetration | |
WFRA45955 | | 300mm diameter | | |
| | | | | | | | | | | | | | | | | |
| | | WP1 | | FR Pl/Board 2 x 1 layer | | -/120/- | | LVH44 | | Mounted in steel casing in penetration | | FCO1870 | | 600mm x 600mm | | |
| | | WP2 | | FR Pl/Board 3 layers | | -/120/- | | LVH44 | | Mounted in steel casing in penetration | | FCO1870 | | 600mm x 600mm | | |
| | | WP3 | | FR Pl/Board 2 x 2 layers | | -/120/- | | LVH-O | | Steel sleeve in penetration | | FCO2203 | | 450mm diameter | | |
| | | WP4 | | FR Pl/Board 25mm liner + 2 layers | | -/120/- | | LVH-O | | Steel sleeve in penetration | | FCO2203 | | 450mm diameter | | |
| | | WP5 | | FR Pl/Board 3 layers + 1 layer pad | | -/120/- | | LVH-O | |
Steel sleeve in penetration | | FCO2203 | | 450mm diameter | | |
| | | WP6 | | FR Pl/Board 3 layers | | -/120/- | | LVH-O | | Steel sleeve in penetration | | FCO2203 | | 450mm diameter | | |
| | | WP7 | | FR Pl/Board 2 x 2 layers | | -/120/- | | LVH44 | | NO casing in penetration | | FCO1854,
FCO2512 | | 600mm x 600mm | | |
| |
| Shaftwall | | WSW1 | | Masonry | | -/120/- | | LVH44 | | Mounted in riser branch (angle free system) | | FCO1869 | | 300 x 300 mm or 90,000mm˛ | | |
| Duct | | WSW2 | | Masonry | | -/120/- | | LVH44 | | Mounted in riser branch tight to slab with packer | | FCO2436 | | 90,000 mm˛ | | |
| | | WSW3 | | Masonry | | -/120/- | | LVH-O | | Mounted in riser branch (angle free system) | | FCO2455 | | 300mm diameter | | |
| | | WSW4 | | FR Pl/Board 3 layers | | -/120/- | | LVH44 | | Mounted in riser branch tight to slab with packer | | FCO2436 | | 300 x 300 mm or 90,000mm˛ | | |
| | | WSW5 | | FR Pl/Board 3 layers | | -/120/- | | LVH44 | | Mounted in riser branch tight to slab with IBS rod & mastic | | FCO2436 | | 300 x 300mm or 90,000mm˛ | | |
| | | WSW6 | | FR Pl/Board 3 layers | | -/120/- | | LVH-O | | Mounted in riser branch (angle free system) | | FCO2455 | | 300mm diameter | | |
| | | WSW7 | | FR Pl/Board 3 layers | | -/120/- | | LVH44 | | Mounted in riser branch (angle free system) | | FCO1869 | | 300 x 300mm or 90,000mm˛ | | |
| | | WSW8 | | FR Pl/Board 2 x 2 layers | | -/120/- | | LVH44 | | Mounted in riser branch (angle free system) | | FCO1869 | | 300 x 300mm or 90,000mm˛ | | |
| | | WSW9 | | FR Pl/Board 2 x 2 layers | | -/120/- | | LVH-O | | Mounted in riser branch (angle free system) | | FCO2455 | | 300mm diameter | | |
| | | WSRF1 | | Retrofit shaftwall option | | -/120/- | | LVH44 | | Retrofit fixing tabs in existing damper housings | | FCO2101 | | 300 x 300mm | | |
| |
| Floor/ | | FL1 | | Concrete slab | | -/120/- | | LVH44 | |
No casing in penetration | | FCO2643/FCO1963 | | Up to 1200mm x >10m or >10m x 1200mm | | |
| Slab | | FL2 | | Concrete slab | | -/240/180 | | LVH44 Cased | |
Steel casing in penetration | | FSP0687 | | 300 x 300mm | | |
| | | FL3 | | Concrete slab | | -/120/120 | | LVH44 | |
Mounted in steel casing in penetration | | FCO1796 | | 600 x 600mm | | |
| | | FL4 | | Concrete slab | | -/120/- | | LVH-O | | Steel sleeve in penetration | | FCO1866 | | 300mm diameter | | |
| | | FL5 | | Concrete slab | | -/120/- | | LVH44 | | NO casing - surface mounted over or under penetration | | FCO1740 | | 600 x 600mm | | max hole size 500mm x 500mm |
| | | FL6 | | Concrete slab | | -/120/- | | LVH-O | | NO steel sleeve in penetration | | F91687 | | 250mm diameter | | |
| | | FL7 | | Concrete slab | | -/120/- | | LVH44 | | Steel casing, modular banked together | | FCO1963 | | 1200mm x 1200mm | | |
| |
| Ceiling | | CE1 | | FR Pl/Board 2 ply Ceiling | | -/60/60 | | LVH44 | | Pl/Board Clad encl. (60min RISF Incipient rated) | | 40904 | | 600 x 600mm | | |
| | | CE2 | | FR Pl/Board 2 ply Ceiling | | -/60/60 | | LVH44 | | Pl/board Clad encl. open end (60min RISF Incipient rated) | | C91474 | | 300mm x 300mm | | exhausting into ceiling void |
| | | CE3 | | FR Pl/Board 2 ply Ceiling | | -/90/90 | | LVH-O | | Pl/board Panel & IFD (90min RISF incipient rated) | | FP3572 | | 150mm diameter | | |
| | | CE4 | | FR Pl/Board 2 ply Ceiling | | -/90/90 | | LVH Hi-Flo | | Pl/board Clad 3 way enclosure (90min RISF Incipient rated) | | FAR2925 | | Incorporates 150mm Hi-Flo | | |
| |
| Door | | FD1 | | LVH-D in Firecore fire doors | | -/120/30 | | LVH-D | | Fitted to Maxi & Mini Fire Doors | | COT388 | | 600 x 300mm or 450 x 450mm | | |
| | | FD2 | | LVH-D in Pyropanel fire doors | | -/120/30 | | LVH-D | | Fitted to Pandor, FR & Pyrolite Fire Doors | | COT442 | | 600 x 600mm, 600 x 300mm, 450 x 450mm | | |
| | | FD3 | | LVH-D in Trafalgar E-Core doors | | -/120/30 | | LVH-D | | Fitted to Maxi & Mini Fire Doors | | FCO1211 | | 600 x 300mm or 450 x 450mm (up to 2 off per leaf) | | |