Penetration SystemBuilding ElementFRLProductApplication / Mounting DetailApproval Ref.Max. SizeCondition
 WallWM1Masonry-/120/-LVH44Mounted in steel casing in penetrationFCO2643, FCO17411200mm x >10m, >10m x 1200mm
 WM2Masonry-/240/-LVH44 Cased Steel casing in penetrationC91525250 x 250mm
 WM3Masonry-/120/-LVH44NO casing in penetrationFCO2643600mm x >10m, >10m x 600mm
 WM4Masonry-/120/-LVH44NO casing - surface mounted over penetrationFCO1740600 x 600mm max hole size 500mm x 500mm
 WM5Masonry-/120/-LVH-OSteel sleeve in penetration 22774-01450mm diameter
 WM6Masonry-/240/-LVH-OSteel sleeve in penetration 22774-01150mm diameter
 WM7Masonry-/120/-LVH-OSSStainless steel sleeve in penetration 22774-01450mm diameter
 WM8Masonry-/120/-LVH-OSpiral duct sleeve grouted into penetration (angle free)FCO2008300mm diameter
 WM9Masonry-/120/-LVH Hi-FloMounted in steel casing in penetrationFCO2568250mm x 400mm
 WM10Masonry-/120/-LVHO Hi-FloSteel sleeve in penetration FCO2568250mm diameter
 WM11Masonry-/120/-LVH44NO casing with various fixing bracketsFCO1854, FC02512600mm x >10m
        
 WH1Hebel 75SS-/120/-LVH44Mounted in steel casing in penetrationFCO23251200 H x 600mm W *dual panel400mm max if in single in panel
 WH2Hebel 75SS-/120/-LVH-O Steel sleeve in penetrationFCO2325450mm dia. *dual panel400mm max if in single in panel
 WH3Hebel 75SW-/120/-LVH44Mounted in steel casing in penetrationFCO23251200 H x 600mm W *dual panel400mm max if in single in panel
 WH4Hebel 75SW-/120/-LVH-O Steel sleeve in penetrationFCO2325450mm dia. *dual panel400mm max if in single in panel
 WH5Hebel 75SW-/120/-LVH44 Mounted in steel casing tight to underside of slabFCO2495300mm x 300mm
 WH6Hebel 75SW-/120/-LVH-O Steel sleeve positioned tight to underside of slabFCO2495150mm diameter
 WH7Hebel 75SW-/120/-LVH44 Mounted in steel casing tight to underside of slab with 3 anglesFCO2495300mm x 300mm
        
 WS1CSR Security wall -/90/90LVH44Mounted in steel casing in penetration WFRA45955600 x 600mm
 WS2CSR Security wall -/90/-LVH-OSteel sleeve in penetration WFRA45955300mm diameter
        
 WP1FR Pl/Board 2 x 1 layer-/120/-LVH44Mounted in steel casing in penetration FCO1870600mm x 600mm
 WP2FR Pl/Board 3 layers-/120/-LVH44Mounted in steel casing in penetration FCO1870600mm x 600mm
 WP3FR Pl/Board 2 x 2 layers-/120/-LVH-OSteel sleeve in penetration FCO2203450mm diameter
 WP4FR Pl/Board 25mm liner + 2 layers -/120/-LVH-OSteel sleeve in penetrationFCO2203450mm diameter
 WP5FR Pl/Board 3 layers + 1 layer pad-/120/-LVH-O Steel sleeve in penetrationFCO2203450mm diameter
 WP6FR Pl/Board 3 layers-/120/-LVH-OSteel sleeve in penetrationFCO2203450mm diameter
 WP7FR Pl/Board 2 x 2 layers-/120/-LVH44NO casing in penetrationFCO1854, FCO2512600mm x 600mm
 
 ShaftwallWSW1Masonry-/120/-LVH44Mounted in riser branch (angle free system)FCO1869300 x 300 mm or 90,000mm˛
 DuctWSW2Masonry-/120/-LVH44Mounted in riser branch tight to slab with packerFCO243690,000 mm˛
 WSW3Masonry-/120/-LVH-OMounted in riser branch (angle free system)FCO2455300mm diameter
 WSW4FR Pl/Board 3 layers-/120/-LVH44Mounted in riser branch tight to slab with packerFCO2436300 x 300 mm or 90,000mm˛
 WSW5FR Pl/Board 3 layers-/120/-LVH44Mounted in riser branch tight to slab with IBS rod & masticFCO2436300 x 300mm or 90,000mm˛
 WSW6FR Pl/Board 3 layers-/120/-LVH-OMounted in riser branch (angle free system)FCO2455300mm diameter
 WSW7FR Pl/Board 3 layers-/120/-LVH44Mounted in riser branch (angle free system)FCO1869300 x 300mm or 90,000mm˛
 WSW8FR Pl/Board 2 x 2 layers-/120/-LVH44Mounted in riser branch (angle free system)FCO1869300 x 300mm or 90,000mm˛
 WSW9FR Pl/Board 2 x 2 layers-/120/-LVH-OMounted in riser branch (angle free system)FCO2455300mm diameter
 WSRF1Retrofit shaftwall option -/120/-LVH44Retrofit fixing tabs in existing damper housings FCO2101300 x 300mm
 
 Floor/FL1Concrete slab-/120/-LVH44 No casing in penetrationFCO2643/FCO1963Up to 1200mm x >10m or >10m x 1200mm
 SlabFL2Concrete slab-/240/180LVH44 Cased Steel casing in penetrationFSP0687300 x 300mm
 FL3Concrete slab-/120/120LVH44 Mounted in steel casing in penetrationFCO1796600 x 600mm
 FL4Concrete slab-/120/-LVH-OSteel sleeve in penetrationFCO1866300mm diameter
 FL5Concrete slab-/120/-LVH44NO casing - surface mounted over or under penetrationFCO1740600 x 600mm max hole size 500mm x 500mm
 FL6Concrete slab-/120/-LVH-ONO steel sleeve in penetration F91687250mm diameter
 FL7Concrete slab-/120/-LVH44Steel casing, modular banked togetherFCO19631200mm x 1200mm
 
 CeilingCE1FR Pl/Board 2 ply Ceiling -/60/60LVH44Pl/Board Clad encl. (60min RISF Incipient rated)40904600 x 600mm
 CE2FR Pl/Board 2 ply Ceiling -/60/60LVH44Pl/board Clad encl. open end (60min RISF Incipient rated)C91474300mm x 300mmexhausting into ceiling void
 CE3FR Pl/Board 2 ply Ceiling -/90/90LVH-OPl/board Panel & IFD (90min RISF incipient rated)FP3572150mm diameter
 CE4FR Pl/Board 2 ply Ceiling -/90/90LVH Hi-FloPl/board Clad 3 way enclosure (90min RISF Incipient rated)FAR2925Incorporates 150mm Hi-Flo
 
 DoorFD1LVH-D in Firecore fire doors-/120/30LVH-DFitted to Maxi & Mini Fire DoorsCOT388600 x 300mm or 450 x 450mm
 FD2LVH-D in Pyropanel fire doors-/120/30LVH-DFitted to Pandor, FR & Pyrolite Fire Doors COT442600 x 600mm, 600 x 300mm, 450 x 450mm
 FD3LVH-D in Trafalgar E-Core doors -/120/30LVH-DFitted to Maxi & Mini Fire DoorsFCO1211600 x 300mm or 450 x 450mm (up to 2 off per leaf)